Early Anomaly-Onset Detection based on Wigner--Ville Distribution Slice Spectra: A Transmission-Grid Test Case

Operational disturbance monitoring in power networks requires decisions to be made from waveform windows as they arrive, rather than from completed records after the event. This study evaluates full-vector Wigner--Ville Distribution Slice (WVDS) spectra for sequential anomaly-onset detection in high-voltage grid-voltage waveforms. The approach keeps the bilinear midpoint interaction structure of the Wigner--Ville distribution and represents each 128-sample voltage window by a 128-dimensional slice spectrum, avoiding manually selected fault-frequency markers. WVDS is used with a baseline-normalized deviation (BND) score and is compared against the BND of Fast Fourier Transform (FFT-BND), r...

AuthorsEduardo Jr Piedad, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt
Primary categoryeess.SP
Published14 June 2026
Last updated at source14 June 2026